Why it matters
CO₂ is produced continuously by occupants and, indoors, it is the most practical single indicator of whether fresh air is actually reaching people. Dubai’s sealed, heavily air-conditioned buildings are designed to keep heat out, which means the same envelope keeps stale air in whenever fresh-air dampers are throttled to save energy.
CO₂ itself is not the hazard at office concentrations. It is a proxy. Where CO₂ climbs, every other occupant-generated contaminant is climbing with it.
World standards
ASHRAE Standard 62.1 sets minimum outdoor air rates per person and per unit floor area rather than a CO₂ number, on the basis that ventilation rate is the thing you control and CO₂ is the thing you observe.
Reference: ASHRAE Standard 62.1, Ventilation and Acceptable Indoor Air Quality.
UAE standards
- CO₂: 800 ppm as an 8-hour average, or 700 ppm above outdoor air levels
- Threshold limit value, ceiling: 5000 ppm
- Carbon monoxide, for comparison: 9 ppm over 8 hours, 25 ppm over 1 hour
A reading persistently above 800 ppm means the fresh-air damper is closed, the intake is blocked, or the space now holds more people than it was designed for. Buildings tested against 1000 ppm can still fail a DM assessment.
Reference: DM-HSD-GU119-IAQ Version 3 (2024), Table 2.
Impact on health
Elevated CO₂ is linked to headache, drowsiness, difficulty concentrating and measurable declines in decision-making performance. Under-ventilated spaces also concentrate airborne pathogens, allergens and VOCs, so the same fault that raises CO₂ raises everything else.
How to fix a building that fails
- Have the fresh-air rate measured against the design specification rather than assumed. DM lists a minimum fresh-air damper opening of around 15% as a check point
- Confirm the outdoor air intake is not blocked, not shielded shut against sandstorms and left that way, and not sited next to a car park exhaust or cooling tower
- Rebalance the air distribution where occupancy has grown since fit-out. DM requires rebalancing after any layout change affecting the HVAC system
- Place monitors in the breathing zone, 1 to 2 m above floor level, away from diffusers and away from anyone’s exhaled breath
- Set the audible alarm at 800 ppm rather than 1000 ppm, so you are warned before the compliance limit rather than after it